Electric Heat
Room facts in, heater out — watts, the feet of baseboard that makes them, and the circuit it lands on.
Estimating only. A dedicated heater circuit is permitted and inspected work — have a licensed electrician run and terminate it.
Heat to install
0
watts · 0 ft of baseboard- Buy
- —
- Room needs
- —
- Current draw
- —
- Circuits
- —
- Wire size
- —
- Cost per hour
- —
One heater covers it. Put it under the window, on the outside wall.
Sizing resistance heat
Electric heat is the one heating system where sizing is straightforward: every watt in becomes a watt of heat, with no efficiency to argue about. The whole question is how many watts the room loses. Ten per square foot covers an insulated room with a standard ceiling in a moderate climate — the figure supply houses have used for decades — and the adjustments above are the three things that reliably break it: thin insulation, single glazing, and a genuinely cold winter.
Once you have watts, the shopping is mechanical, and it involves two different roundings. The room's load is an estimate, so the tag shows it to the nearest 50 watts and no finer. Heaters are another matter: they exist only in fixed sizes, 500 to 2,500 watts, at about 250 watts a foot. The buy list rounds up to the smallest combination that covers the load, with the fewest units, and the feet of baseboard are the feet of those heaters.
Divide the installed watts by volts for amps, add 25 % because heat runs continuously, and you have the breaker — which is the same as saying a circuit may carry heat up to 80 % of its rating. When the heaters will not fit on one circuit the tag splits them and names a breaker and a wire gauge for each. Anything over 1,500 watts should be wired at 240 volts — half the current, smaller wire, and no fighting over a shared circuit — so the calculator offers no 120 volt heaters beyond that.
Where it goes
Under the window, along the outside wall. Cold air falls off the glass and pools on the floor; a heater in that path intercepts it and the room mixes on its own. The same heater on an inside wall heats the ceiling and leaves your feet cold. Split the total between two units if the room has two cold walls.
What it costs to run
Resistance heat is 100 % efficient and still the most expensive way to make heat, because electricity is the expensive energy. A 1,500 watt heater at 17 cents a kilowatt-hour costs about 26 cents an hour, or roughly $90 a month running twelve hours a day. That is the arithmetic that sends people to heat pumps — which move three units of heat per unit of electricity instead of making one.
This is a simplified planning estimate. The implementation does not record a verified NEC edition; no independent licensed review is claimed. A result does not establish code compliance or installation suitability. See electrical sources and limits.
On the counter
The assumptions and limits this calculator uses. The form exposes the settings you can change; fixed allowances are described below.
- Base rate
- 10 watts per square foot, insulated space, 8 ft ceiling
- Adjustments
- Poor insulation +25 %, cold climate +15 %, lots of glass +10 %
- Rounding
- The load is an estimate, shown to the nearest 50 W. The buy list rounds up to heaters that exist
- Heater sizes
- 500 / 750 / 1,000 / 1,250 / 1,500 / 2,000 / 2,500 W at 240 V; 500 / 750 / 1,000 / 1,500 W at 120 V. Fewest units that meet the load, kept close in size
- Baseboard output
- 250 watts per linear foot — the common residential element. Feet are of the heaters bought
- Breaker
- 125 % of the load, because resistance heat is a continuous load, so a circuit carries heat up to 80 % of its breaker
- 120 V limit
- No 120 V heaters offered above 1,500 W
- Wire
- Copper, 60 °C column, sized for the breaker by ampacity only. A long run may need larger wire for voltage drop
Questions from the aisle
How many watts of baseboard heat per square foot?
Ten watts per square foot is the working rule for an insulated room with 8 foot ceilings — 1,500 watts for a 150 square foot bedroom. Poor insulation, a lot of glass, a cold climate or a high ceiling each push it up, which is what the boxes above do.
How long a baseboard heater do I need?
Baseboard puts out about 250 watts per foot, and it is sold as whole heaters, not by the foot: 500, 750, 1,000, 1,250, 1,500, 2,000 and 2,500 watts. A 1,500 watt room takes one 6 foot heater. A room that calculates to 1,900 watts takes a 2,000 watt, 8 foot heater, and one that needs 2,600 takes a 1,500 and a 1,250, 11 feet between them. Two shorter units under the windows beat one long one on an inside wall — heat rises where the cold falls.
120 or 240 volts?
240 volts for anything over 1,500 watts, and this calculator stops offering 120 volt heaters past that point. A 1,500 watt heater draws 12.5 amps at 120 volts and fills a 20 amp circuit by itself; at 240 volts it draws 6.25 and sits on a 15 amp breaker with room for a second heater. A 240 volt heater must be on its own two-pole circuit — it cannot share with receptacles.
Why is the breaker bigger than the amps?
Heat is a continuous load. NEC 210.19(A) sizes the circuit at 125% of it, so a 12.5 amp heater lands on a 20 amp breaker rather than a 15. The tag above has already done that multiplication.
When do I need more than one circuit?
When the heaters add up to more than 80% of the breaker. At 240 volts a 20 amp circuit carries 3,840 watts of heat and a 30 amp circuit 5,760. A 400 square foot room needs 4,000 watts, two 2,000 watt heaters: on 20 amp circuits that is one heater per circuit, each on a 15 amp breaker with 14 AWG copper, or both on one 30 amp circuit with 10 AWG. The largest-breaker setting above chooses between them.
The reasoning behind this one
Wire size, breakers and voltage drop
Where the assumptions above come from, what changes them, and the mistakes that cost a second trip. Free to read, no account needed.