PLANKMATH

Electric Heat

Room facts in, heater out — watts, the feet of baseboard that makes them, and the circuit it lands on.

Estimating only. A dedicated heater circuit is permitted and inspected work — have a licensed electrician run and terminate it.

The space
Conditions

Heater size

0

watts · 0 ft of baseboard
Current draw
—
Breaker
—
Wire size
—
Watts per sq ft
—
Cost per hour
—

Split the wattage between two units under the windows.


Sizing resistance heat

Electric heat is the one heating system where sizing is straightforward: every watt in becomes a watt of heat, with no efficiency to argue about. The whole question is how many watts the room loses. Ten per square foot covers an insulated room with a standard ceiling in a moderate climate — the figure supply houses have used for decades — and the adjustments above are the three things that reliably break it: thin insulation, single glazing, and a genuinely cold winter.

Once you have watts, the shopping is mechanical. Baseboard element runs about 250 watts a foot, so the length follows directly. Divide watts by volts for amps, add 25 % because heat runs continuously, and you have the breaker. Almost anything over 1,500 watts should be wired at 240 volts — half the current, smaller wire, and no fighting over a shared circuit.

Where it goes

Under the window, along the outside wall. Cold air falls off the glass and pools on the floor; a heater in that path intercepts it and the room mixes on its own. The same heater on an inside wall heats the ceiling and leaves your feet cold. Split the total between two units if the room has two cold walls.

What it costs to run

Resistance heat is 100 % efficient and still the most expensive way to make heat, because electricity is the expensive energy. A 1,500 watt heater at 17 cents a kilowatt-hour costs about 26 cents an hour, or roughly $60 a month running twelve hours a day. That is the arithmetic that sends people to heat pumps — which move three units of heat per unit of electricity instead of making one.


On the counter

The assumptions this calculator ships with — every one is adjustable in the form.

Base rate
10 watts per square foot, insulated space, 8 ft ceiling
Adjustments
Poor insulation +25 %, cold climate +15 %, lots of glass +10 %
Baseboard output
250 watts per linear foot — the common residential element
Breaker
125 % of the load, because resistance heat is a continuous load

Questions from the aisle

How many watts of baseboard heat per square foot?

Ten watts per square foot is the working rule for an insulated room with 8 foot ceilings — 1,500 watts for a 150 square foot bedroom. Poor insulation, a lot of glass, a cold climate or a high ceiling each push it up, which is what the boxes above do.

How long a baseboard heater do I need?

Baseboard puts out about 250 watts per foot, so a 1,500 watt room takes 6 feet of element. Two shorter units under the windows beat one long one on an inside wall — heat rises where the cold falls.

120 or 240 volts?

240 volts for anything over about 1,500 watts. The same heat draws half the amps, so it fits a smaller breaker and smaller wire. A 240 volt heater must be on its own two-pole circuit — it cannot share with receptacles.

Why is the breaker bigger than the amps?

Heat is a continuous load. NEC 210.19(A) sizes the circuit at 125% of it, so a 12.5 amp heater lands on a 20 amp breaker rather than a 15. The tag above has already done that multiplication.



Next off the wall

The rest of heating & cooling — most jobs need two or three of these before the first trip to the store.

All heating & cooling calculators Every calculator on the board

The reasoning behind this one

Wire size, breakers and voltage drop

Where the assumptions above come from, what changes them, and the mistakes that cost a second trip. Free to read, no account needed.