PLANKMATH

Service Load

Square footage plus what's plugged into the house, run through the optional dwelling calculation — and the service size that carries it.

Estimating only. A service upgrade is permitted, inspected and usually utility-coordinated work — have a licensed electrician run the calculation for the permit.

The house
Appliances nameplate watts — 0 if gas or absent
Heating and cooling nameplate watts — only the largest one counts
Charging how it counts is a reading of the code, not settled

Service size

100

amp service · calculated load 0 A
General load
—
After demand factor
—
Heating or cooling
—
EV charging
—
Total
—
Headroom
—

At 240 volts, the standard residential service.


How the optional dwelling calculation works

NEC 220.82 exists because the standard method — adding every load at full nameplate — sizes houses for a day that never happens. Nobody runs the range, the dryer, the water heater and the air conditioner in the same minute. So the optional method adds the general load honestly, then discounts it: the first 10,000 VA counts in full, and everything past that counts at 40 %.

The general load is three parts. Three volt-amps for every square foot of conditioned floor area covers lighting and general receptacles. Each 20 amp small-appliance circuit in the kitchen and each laundry circuit adds 1,500 VA. Then every fastened-in-place appliance goes in at its nameplate rating.

Heating and cooling sit outside that discount and get their own rule. They do not run together, so only the largest one is added: air conditioning at 100 %, or a heat pump at 100 % with its backup strips at 65 %, or resistance heat at 65 % of nameplate. A house heated by four or more separately controlled units — a thermostat per room of baseboard — counts that heat at 40 %. The Heating or cooling line on the tag names which one won.

EV charging is the one large load the optional method, through the 2023 edition, leaves unnamed. The Charging setting picks how it counts, the EV charging line on the tag says which reading was used, and the questions below give the difference in amps.

The 2026 edition moves this method to 120.82 and changes its numbers: 2 volt-amps per square foot, the first 8,000 VA in full, and an EV charger at 100 % of nameplate outside the discount. Set the code edition to the one your jurisdiction has adopted; most still enforce an earlier one, which is why 2023 is the default.

Reading the answer

Divide the total by 240 volts and you have the calculated load in amps. Round up to the next service the utility sells — 100, 125, 150, 200 — and check the headroom line. A one-family dwelling may not be served by less than 100 amps in any case (NEC 230.79(C)), so a small house calculating out at 55 amps still gets a 100 amp service. Under about 20 % spare capacity, think hard before adding an EV charger or a heat pump: those are the two loads that turn a comfortable 150 amp service into a 200 amp upgrade.

This is a simplified planning estimate. The implementation does not record a verified NEC edition; no independent licensed review is claimed. A result does not establish code compliance or installation suitability. See electrical sources and limits.


On the counter

The assumptions and limits this calculator uses. The form exposes the settings you can change; fixed allowances are described below.

Method
NEC optional calculation for a dwelling unit: 220.82 through the 2023 edition (default), or 120.82 as the 2026 edition renumbers it
General lighting
3 VA per square foot of conditioned floor area; 2 VA under the 2026 edition
Branch circuits
1,500 VA per small-appliance circuit (two minimum) and per laundry circuit
Demand factor
First 10,000 VA at 100 %, everything above it at 40 %; the first 8,000 VA under the 2026 edition
Heating vs cooling
Only the largest one counts — NEC 220.82(C): air conditioning at 100 %; heat pump at 100 % plus backup heat at 65 %; resistance heat at 65 %, or 40 % with four or more separately controlled units
EV charging
Your setting: 125 % of nameplate outside the demand factor (default), 100 % of nameplate outside it, or nameplate in the general load at 100 %/40 %. 220.82 through the 2023 NEC does not name EV charging; the inspector decides which reading applies. Under the 2026 edition the setting is fixed at 100 % of nameplate
Service floor
100 amps is the code minimum for a one-family dwelling — NEC 230.79(C)

Questions from the aisle

Do I need a 200 amp service?

Less often than people assume. A 1,200 square foot house with gas heat, a gas range and a window unit computes out near 50 amps; 1,800 square feet with an electric range, dryer and central air lands close to 90. Even an all-electric 2,400 square foot house is around 100. What pushes a service past 150 is a Level 2 EV charger, a heat pump with resistance backup, or both: a 9,600 watt charger adds 50 amps at the default setting below (40 or 16 at the other two), and swapping a 4,000 watt air conditioner for a heat pump with 15 kW of backup strips adds about 40.

Is this the same calculation an electrician does?

It is the optional method in NEC 220.82 (120.82 in the 2026 edition), the one used for most existing dwellings. The standard method in 220.42 through 220.55 applies different demand factors appliance by appliance and sometimes lands lower. An electrician doing a service upgrade will run one of the two on paper for the permit.

Which code edition should I pick?

The one your jurisdiction has adopted, which the building department or your electrician can tell you. Most places still enforce the 2023 or 2020 edition, so that is the default here. The 2026 edition renumbers the method to 120.82 and changes three numbers: general lighting drops from 3 to 2 VA per square foot, the tier counted in full shrinks from 10,000 to 8,000 VA, and an EV charger is added at 100 % of nameplate outside the demand factor. For the default 1,800 square foot house that moves the calculated load from 96 amps to 88; with a 9,600 watt charger, from 146 to 128. The 2026 figures here come from published summaries of that edition, not from the code text.

What counts as an appliance load?

Nameplate VA of everything fastened in place or on its own circuit: range, wall oven, cooktop, dryer, water heater, dishwasher, disposal, microwave, well pump, hot tub. Portable things you plug into a general receptacle are already covered by the square-footage allowance. EV charging gets its own field above, with a choice of how it is counted; the next answer explains the three.

How is the EV charger counted?

However you set it under Charging, because NEC 220.82, through the 2023 edition, never mentions EV charging and electricians and inspectors read it three ways. At 125 % of nameplate outside the demand factor, the default, a 9,600 watt charger counts as 12,000 VA and adds 50 amps. That reading leans on 625.42 calling charging a continuous load, though that sentence is written for Article 625 itself, not the load calculation. At 100 % of nameplate outside the demand factor, the same charger adds 40 amps. Counted as one more fastened-in-place appliance in the general load, it adds 16 amps in any house whose general load is already past 10,000 VA, which is nearly every house with an electric range or dryer, because all of it lands in the 40 % tier. The 2026 NEC, which moves the optional method to 120.82, adds an EV line at 100 % of nameplate with no demand factor, the middle setting; the same edition also lowers the lighting allowance and the first demand tier, which this calculator does not follow. The standard method is separate again: 220.57 in the 2023 NEC counts a charger at 7,200 VA or its nameplate, whichever is larger. Your inspector decides which reading applies where you live, so if the setting is the difference between keeping your service and upgrading it, ask before you buy.

Why does electric heat count at only 65 % or 40 %?

Because that is how the optional method treats it. The largest single item out of these is added: air conditioning at 100 %, a heat pump at 100 % plus its backup heat at 65 %, or resistance space heat at 65 % of nameplate. With four or more separately controlled heating units, typically a thermostat in each room, the heat counts at 40 % instead, because they never all call at once. For 12,000 watts of baseboard that is 7,800 VA with one to three thermostats and 4,800 VA with four or more.

Why is my panel full but my load fine?

Breaker spaces and amperage are unrelated. A 100 amp panel with twenty full slots can be well under its calculated load while having nowhere left to land a wire. Tandem breakers or a subpanel solve spaces; only a service upgrade solves amps.



Next off the wall

The rest of electrical — most jobs need two or three of these before the first trip to the store.

All electrical calculators Every calculator on the board

The reasoning behind this one

Does my panel have room for it

Where the assumptions above come from, what changes them, and the mistakes that cost a second trip. Free to read, no account needed.