Wire Size
Load in amps, distance in feet, and the gauge that satisfies both the ampacity table and the drop over the run.
Estimating only. Electrical work is permitted and inspected against the code edition adopted where you live — have a licensed electrician do or verify the work.
Buy this wire
12
AWG copper · 20 A breaker- Ground wire
- —
- Sized for
- —
- Termination column
- —
- After derating
- —
- Voltage drop
- —
- Volts at the load
- —
Sized by the ampacity table.
How wire sizing works
Two separate questions decide the gauge. The first is heat: NEC Table 310.16 lists how many amps a conductor may carry continuously without cooking its insulation, in three columns for 60, 75 and 90 °C terminations. The second is distance: every foot of copper has resistance, and a long run arrives at the load with less voltage than it left with. Short circuits are decided by the table; long ones are decided by the drop.
One rule overrides the table for small wire. NEC 240.4(D) will not let a 14 AWG copper conductor sit behind more than a 15 amp breaker, or 12 AWG behind more than 20 amps, however generous the 90 °C column looks. That is why a 20 amp kitchen circuit is 12 AWG and not 14 AWG — the table alone would have allowed it.
Derating: hot air and crowded conduit
The table assumes 86 °F air and no more than three current-carrying conductors together. Hotter air or more conductors in one conduit or cable cut the ampacity by the factors in NEC 310.15, and those factors are applied to the column the insulation is rated for — the 90 °C column for THHN, XHHW-2 and the conductors inside NM-B cable. The derated figure is then compared with the termination column and the smaller of the two governs, so a 12 AWG conductor derated from 30 amps to 21 is still good for 20, while one derated to 15 is not. Grounds do not count as current-carrying, and neither does a neutral that only carries the imbalance between two hots. Leave the two boxes at 86 °F and 2 and nothing is derated.
Common branch circuits
| Circuit | Copper | Ground | Breaker | Typical use |
|---|---|---|---|---|
| 15 A | 14 AWG | 14 AWG | 15 A | Lighting, bedroom receptacles |
| 20 A | 12 AWG | 12 AWG | 20 A | Kitchen, bathroom, garage receptacles |
| 30 A | 10 AWG | 10 AWG | 30 A | Dryer (240 V), water heater |
| 40 A | 8 AWG | 10 AWG | 40 A | Range, EV charger |
| 50 A | 6 AWG | 10 AWG | 50 A | Range, welder, hot tub |
| 100 A | 3 AWG | 8 AWG | 100 A | Subpanel feeder (75 °C terminations) |
Why the run length changes the answer
The drop is proportional to current times distance divided by the conductor's area, so doubling the run doubles the loss. A 20 amp circuit at 120 volts is fine on 12 AWG for the first 50 feet or so; run it 120 feet out to a workshop and the same wire arrives several volts short, dimming lights and making motors run hot. The calculator bumps the gauge until the drop fits your limit and says which of the two constraints decided it.
This is a simplified planning estimate. The implementation does not record a verified NEC edition; no independent licensed review is claimed. A result does not establish code compliance or installation suitability. See electrical sources and limits.
On the counter
The assumptions and limits this calculator uses. The form exposes the settings you can change; fixed allowances are described below.
- Ampacity table
- NEC 310.16 — the 60/75/90 °C columns for copper and aluminum, 14 AWG to 500 kcmil
- Small-conductor rule
- NEC 240.4(D): 14 AWG Cu capped at 15 A, 12 AWG at 20 A, 10 AWG at 30 A
- Continuous loads
- Sized at 125 % when the box is ticked — NEC 210.19(A). Checked against the termination column, not stacked on the derating
- Ambient correction
- NEC Table 310.15(B)(1), applied to the insulation column. 78–86 °F is 1.00
- Bundling adjustment
- NEC Table 310.15(C)(1): 4–6 current-carrying conductors 80 %, 7–9 70 %, 10–20 50 %, 21–30 45 %, 31–40 40 %, 41 or more 35 %
- Breaker
- Next standard size at or above the design current, and never more than one standard size above the derated ampacity — NEC 240.6(A), 240.4(B)
- Ground wire
- NEC Table 250.122 by breaker rating, same metal as the circuit, enlarged in proportion when the run forces a bigger conductor — 250.122(B)
- Supply
- 120 or 240 V single phase, the two a house has
- Voltage drop
- 3 % branch-circuit target — a recommendation in NEC 210.19 informational notes, not a rule
Questions from the aisle
What size wire do I need for a 20 amp circuit?
12 AWG copper. NEC 240.4(D) caps 14 AWG copper at a 15 amp breaker and 12 AWG at 20 amps regardless of what the ampacity table says, so a 20 amp circuit starts at 12 AWG — and gets bigger if the run is long enough for voltage drop to bite.
What size wire for a 100 amp subpanel 150 feet away?
Set the form to 240 volts and 75°C terminations. Ampacity alone allows 3 AWG copper at 100 amps, and at 100 feet that is the answer. Stretch it to 150 feet and the drop passes 3%, so the calculator bumps it to 2 AWG; at 200 feet it goes to 1 AWG. The ground grows with it, from 8 AWG to 6 AWG to 4 AWG. That progression is the whole reason to enter the distance rather than look the size up in a table.
Which temperature column should I use?
NEC 110.14(C) sizes conductors by the lowest-rated termination in the circuit. For equipment rated 100 amps or less that is the 60°C column unless the breaker and lugs are both marked for 75°C — which most modern panels are. This form defaults to 60°C, the conservative reading.
When does derating change the wire size?
Less often than the factors suggest, because they come off the 90°C column and most circuits are held to the 60 or 75°C column anyway. Seven current-carrying 12 AWG conductors in one conduit are adjusted to 70%: 30 amps becomes 21, still enough for a 20 amp circuit. Ten of them are adjusted to 50%, which is 15 amps, and the same circuit moves up to 10 AWG. A 130°F attic alone leaves 12 AWG at 22.8 amps; the same attic with four conductors bundled together takes it to 18.2, and again the answer is 10 AWG.
What size ground wire do I need?
It follows the breaker, not the load: 14 AWG copper on a 15 amp breaker, 12 AWG on 20 amps, 10 AWG from 30 through 60 amps, 8 AWG up to 100 amps and 6 AWG up to 200 amps. Aluminum grounds run one step larger. When the circuit conductors are enlarged for voltage drop the ground is enlarged in the same proportion, which is why a 20 amp circuit pulled 100 feet on 8 AWG gets an 8 AWG ground.
Is aluminum wire allowed?
Aluminum is still used for services and feeders, and it is cheaper per amp. It needs a size or two larger for the same load, listed connectors (AL/CU rated), and antioxidant paste at the terminations. It is rarely worth it for a small branch circuit.
The reasoning behind this one
Wire size, breakers and voltage drop
Where the assumptions above come from, what changes them, and the mistakes that cost a second trip. Free to read, no account needed.